Nebius's August 27 postmortem describes an August 19 cooling failure at the facility hosting U.S. Central One. A storm-related failure disabled the building-management system and chilled-water loop; equipment shut down on thermal protection. Cooling stabilized after roughly six hours, but restoring resources took longer.
Automatic VM recovery made one attempt per instance, with rate limits intended for isolated failures. Roughly a third of running VMs were affected, and roughly a third of their initial recovery attempts succeeded. Stale disk attachments caused many failures. Engineers later cleared the storage state, but already-spent recovery attempts did not automatically restart.
A hot-plug bug separately left some secondary disks unattached. Kubernetes control-plane instances could return without their state disks, leaving clusters unhealthy. Controlled stop-starts restored affected clusters, and Nebius says the fix was deployed across regions. Existing inference traffic elsewhere continued, while new deployments and autoscaling were degraded through regional dependencies.
The failed building-management system was also meant to raise the cooling alarm. Temperature rises appeared retrospectively in dashboards from about 09:15 UTC; component-overheating alerts prompted action at 10:15. Nebius calls for environmental alerts independent of that system.